    2000A 12KV Withdrawable Circuit Breaker Modularized Mechanism

    VS1-12 withdrawable Vacuum Circuit Breaker 12KV 630-2000A

    Voltage: 12KV

    Current: 2000A

    Breaking current: 20KA

    Type: withdrawable


    Product overview

    VS1-Series circuit breakers are complete independently developed by Knkong based on the advanced design concept; it adopts a modularized mechanism, which is easy for installation, maintenance, testing, and operation. As compared with conventional VS1 circuit breaker. it features higher operation stability, higher safety, and extended service life. The product can satisfy customers demand application in 12kv and 24kV power transmission and distribution systems, which is extensively applied in such industries as power, energy, petrochemical engineering, metallurgy, manufacture, traffic, building, and environmental protection as well as large-scale enterprises and national key projects


    Normal service condition

    Altitude≤1000m
    Ambient temperatureMax+40℃
    Min-15℃

    Ambient humidity:

    Maximum average humidity

    24 hours ≤95%
    1 month ≤90%
    Maximum water vapor pressure24 hours ≤2.2kpa
    1 month ≤1.8kpa

    Special service condition

    For special operating conditions, please consult the manufacturer:
    The site altitude exceeds 1000m
    -Allows to reduce the dielectric strength of air
    -Or order a high prototype circuit breaker, which should meet
    Corresponding insulation requirements.
    Ambient temperature rise
    -Reduced current carrying capacity
    -Provide additional ventilation for heat dissipation
    Other precautions should be negotiated with the manufacturer according to section 2.2 of IEC 62271-1

    Technical Parameters

    No.ItemUnitParameter
    1Rated voltageKV12
    2Rated frequencyHz50/60
    3

    Rated insulation level

    1min power frequency withstand voltage(r. m. s)

    KV

    42(phase-to-phase, phase-to-earth)

    48(across the isolating distance)

    Lighting impulse withstand voltage (peak)

    75(phase-to-phase, phase-to-earth)

    85(across the isolating distance)


    4


    Rated current


    A

    63063012501600
    1250125016002000
    20002500
    25003150
    4000
    5Rated short-circuit breaking current

    KA

    202531.540
    6Rated short-time withstand current202531.540
    7Rated short-circuit marking current506380100
    8Rated peak withstand current506380100
    9Rated duration of short-circuits4
    10Rated operating sequenceO-0.3s-O/C-180s-O/C
    11Breaking times of rated short-circuit currentTimes30/20 times(40KA)
    12Mechanical enduranceOps20000
    13Rated single capacitor bank breaking current

    A

    630
    14Rated back-to-back capacitor bank breaking current400
    15Double-earth fault breaking current27.4
    16Allowable maximum contact erosion

    mm

    3
    17Clearance between open contacts10±1
    18Over stroke3.5±0.5
    19Non-simultaneity of 3-phase opening and closing

    ms


    ≤2
    20Bounce duration of contact closing≤2
    21Average breaking speed (instant breaking 6mm)

    m/s


    1.1±0.2
    22Average making speed0.8±0.2
    23Making time

    ms


    ≤100
    24Breaking time≤50

    25


    Resistance of each phase main circuit


    μ Ω

    630A≤50
    1250A≤45
    1600A~2000A≤35
    ≥2500A≤25
    26Contact breaking bounce amplitudemm≤2

    27

    Rated operating voltageRated operating voltage(V)AC/DC

    V

    24*110220
    Scope of normal operation voltageOpening:65%-120% rated voltage, in case the voltage is lower than 30% rated voltage, opening operation is not allowed
    28Rated voltage of energy storage motorVAC110/220,DC110/220
    29Energy storage timeS≤15

    Operation safety

    With anti-maloperation locking protection these circuit breakers, working in switchgear cabinets, can realize "five-protection" interlocking functions, avoiding malapert and maximizing the protection of an operator's personal safety.

    Only when the circuit breaker and earthing switch are in the disconnected position can the truck of circuit breaker be racked to the service position from the test position

    The circuit breaker can be closed only when in the service/test position.

    With the circuit breaker closed its truck cannot be racked in or racked out which can be realized only when the circuit breaker is in the disconnected position.

    The circuit breaker in a closed position cannot be racked out from the service position to the test position.

    The circuit breaker cannot be closed while it is being racked in.

    When the circuit breaker is closed, if the closing signal fails to be removed timely, the internal anti-trip control circuit will cut off the closing circuit to prevent multiple reclosing (optional).

    If the electric closing lockout is selected, the circuit breaker will be unable to be closed when the secondary circuit fails to provide power or the power provided fails to meet the normal operation of the locking electromagnet(optional).